solalogo.gif (2604 bytes)

Alfa Home  Products  Supports  Contact Us

PAGE BY ALFA COMPUTERS
SOLA 610  UPS

700VA to 10kVA
50/60Hz Single Phase UPS and 7.5kVA to 20kVA 50/60 Hz 3 Phase Input/Single Phase Output UPS

COMPLETE PROTECTION AGAINST POWER PROBLEMS

SOLA 610 SERIES UPS

FEATURES AND BENEFITS
On-Line Double Conversion UPS
On-line pure sine wave technology for perfect mains voltage reproduction and regulation.
Inbuilt Bypass Facility
An internal automatic bypass protects the UPS from extreme overloads and critical load from UPS shutdown.
SNMP Adaptor
On board SNMP Adaptor option simplifies network management interfacing.
Communication Options
Apart from standard network and RS232 outputs, the SOLA 610 includes CheckUPS II® Software to allow interface to most popular operating systems. Convenient standard cable included. AS400® interface card option can be fitted to the communications slot in addition to the standard network and RS232 outputs.
User Friendly
Simple to operate front mounted controls, functional LED indicators, UPS Load/Battery Capacity Bargraph and Mimic Diagram.
Add on Battery Capability
Optional battery packs are available to provide extended run times for critical applications. Contact SOLA for more details.
2 Year Warranty
Full two year warranty. Optional Extended Warranty and Service Plans available.
Safety Approved
Complies with TUV, CSA, UL and CE Standards.

PRODUCT SELECTION

Capacity
(VA)

Freq.
(Hz)

Input & Output
Voltage

Backup Time
(Half) Full Load

Mass
(kg)

Height
(mm)

Width
(mm)

Depth
(mm)

Part No.

700

50 / 60

240/240V AC

(11) >5 minutes

11.5

225

145

405

610-0700-A

1000

50 / 60

240/240V AC

(17) >8 minutes

15

225

145

405

610-1000-A

2000

50 / 60

240/240V AC

(22) >10 minutes

33

350

192

455

610-2000-A

3000

50 / 60

240/240V AC

(11) >5 minutes

35

350

192

455

610-3000-A

6000

50 / 60

240/240V AC

(25) >8 minutes

115

710

260

555

610-6000-A

10000

50 / 60

240/240V AC

(30) >12 minutes

200

980

340

656

610-010K-A

7500

50 / 60

415/240

(46) 17

180

980

656

340

061007k53

10000

50 / 60

415/240

(31) 10

180

980

656

340

0610010k3

15000

50 / 60

415/240

N/A

126

965

670

380

0610015k3

20000

50 / 60

415/240

N/A

126

965

670

380

0610020k3

 

Personal computers, LAN servers and telecommunications equipment can function erratically and fail without warning if the quality of the electrical supply source is poor. Other critical equipment such as industrial process control and CAD/CAM equipment can also shutdown unexpectedly if backup power is not provided.

Whether you experience a power disturbance or outage, your SOLA 610 UPS system will constantly protect your critical load. Electrical noise is attenuated to safe levels and the smooth output voltage is tightly regulated. When utility mains is available, internal sealed lead acid maintenance free batteries are automatically charged, ready for use when mains disturbances occur.

The SOLA 610 advanced PWM on-line sine wave UPS system features an automatic bypass line and sealed batteries, inside a stylish compact enclosure. All units feature LAN/WAN interface capability, communications slot for on board SNMP adaptor or AS400® interface card, high and low voltage protection and transient surge protection to international standards.

SOLA 610 models up to 3kVA come with a flexible input cable and outlet sockets; 7.5, 10, 15 and 20kVA have hardwired connections.

The SOLA 610 includes a unique start up functional test for security of operation.

Typical applications include

File Servers
LAN/WAN equipment
Telecommunications
Industrial Control Systems
Security Systems
Mid Range Computers

SPECIFICATION

INPUT
Single Phase: Nominal Voltage 240 Volts AC (other voltages available)
Three Phase In/Single Phase Out: 415 Volts A/C (other voltages available)
Input Range 187 - 264V AC - Single Phase
304-456 VAC - Three Phase In/Single Phase Out
Frequency 50/60 Hz (Auto Selecting) + 5%

OUTPUT
Waveform Pure Sinewave
Voltage 240 Volts AC factory setting (user selectable to 208, 220 or 230V)
Inverter Voltage Nominal ±3%, full linear load
Transient Condition ±6% for 100% to 20% or 20% to 100% variation in resistive load
Inverter Frequency 50/60 Hz (same as input, mains present). Nominal ±0.5% (Inverter Free Running)
Harmonic Distortion < 4% THD @ full linear load
Overload Capacity 130% for 1.5 seconds
Surge Attenuation IEEE/ANSI C62.45-1991 to 6kV
Efficiency > 80% (full load @ 0.7 pf, fully charged batteries)

BATTERY
Type Sealed, maintenance free
Recharge Time Fully discharged UPS internal batteries recharged to 90% in 8 hours

STATUS INDICATORS AND CONTROLS
Front Panel UPS ON/OFF and Alarm Silence Push Buttons. LED indication of - AC Line
Available; Bypass; Inverter On; Fault; Load Levels; Battery Capacity
Audible Alarms Battery Discharging (sounds every 4 seconds on mains failure).
Low Battery/Overload (sounds once per second).
UPS Fault (sounds continuously).

ENVIRONMENTAL
Operating Temperature 0°C to 40°C < 1500 m altitude
Storage Temperature -15°C to +45°C
Note: High temperatures reduce battery life.
Relative Humidity 20 - 95%, non condensing
Acoustic Noise Level < 50 dBA @ 1 m (model dependent)

COMPUTER INTERFACE
Networking Outputs: Provided by DB9 for AC OK, AC Failure and Low Battery
Inputs: Inverter Shutdown
RS232 Available via DB9 connector for computer interface
Communications Slot Allows user installed optional cards to be fitted
(a) AS400® Card (Part No. 0610AS400)
(b) SNMP Card (Part No. 0610SNMP)
(c) Bestlink® Card (Part No. 0999IPK0319B)
Software CheckUPS II® software/cable included. Suits most common operating systems (Windows 95®, Windows NT®, various UNIX systems, Novell® etc.)

WARRANTY
Full two year Warranty.
Extended Warranty and Service Plans available.

Alfa Home  Products  Supports  Contact Us